1
RO UltraTec - The Ultra Solution
 
 

AT-Series RO Systems - 500 to 1000 Gallons Per Day

R.O. UltraTec™ AT-Series Reverse Osmosis Systems feature a compact design and only measure 18" in depth, 20" in width and 27" in height. Systems have their prefilters, instrumentation and pressure indicators strategically located in front for ease of service and monitoring. R.O. UltraTec™ AT-Series Reverse Osmosis Systems are ideal for light commercial applications with feed water up to 2000 TDS and requiring up to 1000 gallons per day.

STANDARD FEATURES

  • Manual On/Off Control Switch
  • Powder Coated Aluminum Frame
  • 5 Micron Sediment Prefilter
  • 10 Micron Carbon Block Prefilter
  • Double O-Ring Filter Housings
  • Brass Rotary Vane High Pressure Pump
  • Carbonator High Efficiency Motor
  • Low Energy TFC Membrane Elements
  • PVC Membrane Housings
  • Permeate and Concentrate Flow Meters
  • Low Pressure Switch
  • Feed Solenoid Valve with Manual Bypass
  • Stainless Steel Concentrate Valve
  • 0-300 psi Pump Pressure Gauge
  • 0-160 psi Prefilter Pressure Gauges
  • Push/Pull Fittings with Locking Safety Clips
  • Identification of Components
  • Factory Tested & Preserved
  • CE Compliant
  • Made in the U.S.A

 

-----------------------------------------
Reverse Osmosis Systems
-----------------------------------------
Media Filtration
-----------------------------------------
Membrane Elements
-----------------------------------------
Membrane Housings
-----------------------------------------
Filter Cartridges
-----------------------------------------
Filter Housings
-----------------------------------------
Pumps
-----------------------------------------
Motors
-----------------------------------------
UV Sterilizers
-----------------------------------------
Ozone Generators
-----------------------------------------
Chemical Pumps
-----------------------------------------
Chemicals
-----------------------------------------
Instruments
-----------------------------------------
Test Equipment
-----------------------------------------
Components
-----------------------------------------

 

 

Model

GPD

Membranes

Motor HP

Unit Specifications

Download Brochure

Size

Qty

60Hz

Dimensions

Weight

AT-500

500

2.5" x 21"

2

1/3

18" x 20" x 27"

65 lbs.

 

AT-1000

1000

2.5" x 21"

3

1/2

18" x 20" x 27"

70 lbs.

 

*Systems available in 110V 60Hz 1 Phase, 220V 60Hz 1 Phase, 220V 50Hz 1 Phase**.
**50Hz systems must be ordered with Extra Low Energy Membrane Elements.

ECONOMY PACKAGE FEATURES

  • All Standard Features

PLUS PACKAGE FEATURES

  • Minitrol Computer Controller
  • LED Display
  • Pre-Treatment Lockout
  • Tank Level Input
  • Concentrate Recycle
  • Concentrate Recycle Flow Meter
  • Permeate TDS Monitor
  • Extra Low Energy TFC Membrane Elements
  • Includes All Other Standard Features

DELUXE PACKAGE FEATURES

  • Minitrol IF Computer Controller
  • LED Display
  • Pre-Treatment Lockout
  • Tank Level Input
  • Concentrate Recycle
  • Concentrate Recycle Flow Meter
  • Permeate and Feed TDS Monitor
  • Extra Low Energy TFC Membrane Elements
  • Auto Flush
  • Stainless Steel Pump
  • Includes All Other Standard Features

OPTIONS TO BE ORDERED SEPARATELY

  • High Pressure Storage Tank Switch 110/220V
  • Normally Closed Storage Tank Float Switch 110/220V
  • Wooden Crate

NOTES

  • All dimensions and weights are approximate.
  • All systems come packaged in a cardboard box. Wooden crating is optional.
  • For feed water exceeding 2000 TDS, a water analysis is required and the system's standard configuration may
    be required to change based on the manufacturer's recommendations.
  • The proper pre-treatment before the reverse osmosis system is required in order to obtain the maximum life
    from the reverse osmosis membrane elements. That means that all Chlorine must be removed prior to the system
    if present in the feed water. Feed water should be treated by a water softener or antiscalant to avoid scaling or
    premature failure of the membranes. All other pretreatment required to treat particular contaminants in the feed water
    should be added by the customer accordingly.